Wuhan Unique Mechanical And Electrical Equipment Co.,LTD.

Wuhan Unique Mechanical And Electrical Equipment Co., LTD.

Manufacturer from China
Site Member
6 Years
Home / Products / Eltek Rectifiers /

High Stable Flatpack2 48v 2000w Super HE Eltek Rectifier Module 241115.106

Contact Now
Wuhan Unique Mechanical And Electrical Equipment Co.,LTD.
City:wuhan
Province/State:hubei
Country/Region:china
Contact Person:MrCocoon Lee
Contact Now

High Stable Flatpack2 48v 2000w Super HE Eltek Rectifier Module 241115.106

Ask Latest Price
Video Channel
Brand Name :Eltek
Model Number :241115.106
Place of Origin :China
Certification :CE, RoHS
MOQ :1 set
Price :negotiable
Packaging Details :carton box
Delivery Time :within 10 days of payment
Payment Terms :L/C, T/T
Supply Ability :1000 sets/month
Model :48/2000 SHE
Part number :241115.106
Frequency :45 - 66 Hz
Max power, de-rated :850 W
Maximum current :11.6 ARMS
MTBF :1 900 000 hours
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Flatpack2 48V 2000W Super HE Eltek Rectifier Module 241115.106

Super High Efficiency (SHE) rectifiers for Telecom applications

The Flatpack2 48V Super HE rectifiers are contributing to setting the new industry standard for efficiency in the DC power market.

With an efficiency of 97.8% the Super HE is a premium rectifier particularly suitable for markets and applications where the energy is costly. In grid connected applications the payback time is down to 2 years compared to standard HE rectifiers, and in hybrid applications even faster.

The Flatpack2 Super HE is fully compatible with Flatpack2 and Flatpack2 HE systems and can replace any Flatpack2 48V rectifier module.

APPLICATIONS

TELECOM - WIRELESS

Radio base station / Cell sites

LTE / 4G / WiMAX

Mobile switching center (MCS)

Microwave

Broadband

TELECOM - FIXED

Central office

Telephony servers / switches

Fiber optics

Microwave

Broadband

Broadcast

Data center

Key Features

SUPER HIGH EFFICIENCY – 97.8%

HIGH POWER DENSITY – 33 W/IN3

COMPATIBLE WITH EXISTING SYSTEMS

GLOBAL COMPLIANCE

PATENTED TECHNOLOGY

HOT PLUGGABLE

Specifications

Model 48/2000 SHE
Part number 241115.106
INPUT DATA
Voltage (nominal range) 185 - 264 VAC
Voltage (operating range) 85 - 264 VAC
Frequency 45 - 66 Hz
Maximum current 11.6 ARMS
Protection Fuse in Live, varistor for transient protection, shutdown when VIN is out of range
OUTPUT DATA
Voltage (default) 53.5 VDC
Voltage (adjustable range) 43.21) - 57.6 VDC
Max power, nominal input 2000 W
Max power, de-rated @VIN = 85 VAC 850 W
Max current, @VOUT = 48 VDC 41.7 A
Current sharing ±5.0% of max current
Static voltage regulation (10-100% load) ±0.5%
Dynamic voltage regulation ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Hold up time (3000W load) >10ms; output voltage > 42 VDC
Ripple <150 mVPP , 30 MHz bandwidth

Protection

Overvoltage shutdown, short circuit proof, high temperature, hot plug-in inrush current limiting, fuse
OTHER SPECIFICATIONS
Peak Efficiency 97.8 %

Isolation

3.0 kVAC – input to output

1.5 kVAC – input to protective earth

0.5 kVDC – output to protective earth

Alarms (Red LED)

Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure

Warnings (Yellow LED)

Rectifier in power derate mode, Remote current limit activated, Input voltage out of range, flashing at overvoltage
Normal (Green LED) Input and output ok
MTBF (Telcordia SR-332 Iss.3 method II Case L1) 1 900 000 hours
Operating temperature (5 - 95% RH non-cond.) -40 - 75°C [-40 - 167°F ]
Max output power de-rates above temp / to 45°C [+113°F] / 1350 W
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.0 x 327mm [4.25 x 1.61 x 13”] / 2.050 kg [4.5lbs]
DESIGN STANDARDS
Electrical safety EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014
EMC

EN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019

ETSI EN 300 386 V.2.1.1, FCC CFR 47 Part 15:2013

Environment

ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)

Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised

1) Stand-by / test operation (VOUT < 48VDC) limited for VIN > 230 VAC

2) When input mains voltage is below 210 VRMS temperature derating will start at 40 °C and 1500 W will be available at 75 °C